GD-B series surge protector device(in short:SPD,alias:surge protector,surge arrester) is suitable for TN-S, TN-C-S, TT, IT etc. Power supply system of AC 50/60Hz,≤380V, ans installed on the joint of LPZOA zone or LPZOB and LPZ1 zone, which protects the electric network not shocked by the thunder, it's designed according to GB18802.1, IEC61643-1, it adopts 35mm standard rail, there is a failure release mounted on the module of surge protective device, when the SPD fails in breakdown for over-heat and over-current, the failure release will help electric device separate from the power system and give the indication signal,green means normal,red means abnormal, it's also could be replaced for module when has operating voltage.
Intensity of Remote Signalling Alarm Contact
Failure indication and centralized remote signalling alarm dry contacts;
High discharge capacity and low residual voltage;
Over-temperature protection;
IP20, UL94 V0
Model | GD-B | ||
Rated Operating Voltage Un(V) | 220V 380V | 220V 380V | 220V 380V |
Maximum Continuous Operating Voltage Ue(V) | 385V 420V | 385V 420V | 385V 420V |
Voltage Protection Level Up(kV) | ≤2.8 ≤3.2 | ≤2.2 ≤2.5 | ≤2.0 ≤2.3 |
Nominal Discharge Current In(8/20μs)kA | 60 | 40 | 30 |
Maximum Discharge Current Imax(8/20μs)kA | 100 | 80 | 60 |
Response Time ns | <25 | ||
The cross Section of L/N Line(mm²) | 16,25 | 10,16 | 10,16 |
The cross Section of PE Line(mm²) | 25,35 | 25 | 16,25 |
Fuse or Switch (A) | 63A | 63A | 63A,32A |
Operating Environment ºC | -40ºC ~ +85ºC | ||
Relative Humidity (25ºC) | ≤95% | ||
Installation | Standard Rail 35mm | ||
Meterial of Outer Covering | Fiber glass reinforced plastic |